SF6 Air insulated switchgear GSM Modular Units up to 36kV

Using SF6 gas as insulation and arc extinguishing medium, rotating arc and
arc extinguishing of a constant magnetic field make the arc esxtinguishing capability
free from the influence by the arc current,pefect breaking performance,weak overvoltage,
long electrica life span, arc chamber maintenance-free.
High quality GSC series (SC6-SIC type, SC6-SQC type) Indoor SF6 LBS, composite apparatus.
Three-position, multi-functions; easy operation, high reliability operation mechanism and lock,
with a small gas pressure gauge. Passed SF6 gas zero pressure rated breaking test,
super functional , high reliability.Earthing switch has the short-circuit making capability
which corresponds to national standard.
Rated voltage
|
Ur
|
kV
|
|
7.2
|
12
|
17.5
|
24
|
36
|
Insulation level
|
Insulation
|
Ud
|
50/60Hz,1 min(kV rms)
|
20
|
28
|
38
|
50
|
70
|
Isolation
|
Ud
|
50/60Hz,1min(kV rms)
|
23
|
32
|
45
|
60
|
80
|
Insulation
|
Up
|
1.2/50 μs(kV peak)
|
60
|
75
|
95
|
125
|
170
|
Isolation
|
Up
|
1.2/50μs (kVpeak)
|
70
|
85
|
110
|
145
|
195
|
Breaking capacity
|
Transformer off load
|
|
A
|
|
16
|
Cables off load
|
|
A
|
|
31.5
|
50
|
Rated current
|
Ir
|
A
|
|
630
|
Short-time withstand current
|
lk/tk ⑴
|
kA/1 s
|
25
|
630
|
|
|
|
20⑵
|
630
|
|
|
|
16
|
630
|
|
|
|
12.5
|
630
|
Making capacity (50 Hz)
|
Ima
|
kA
|
62.5
|
630
|
|
NA
|
|
|
|
|
|
50
|
630
|
|
|
|
40
|
630
|
|
|
|
31.25
|
630
|
Maximum breaking capacity (Isc)
|
Units IM,IMC,IMB
|
|
A
|
|
630
|
QM.QMC, QMB
|
|
kA
|
|
25
|
|
20
|
|
20
|
PM
|
|
kA
|
|
25
|
20
|
Vacuum circuit breaker range
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DMV-A, DMV-D, DMV-S
|
kA
|
25
|
630
|
N/A
|
|
|
|
|
DMVL-A
|
kA
|
20
|
630
|
NA
|
|
|
DMVL-D
|
kA
|
25
|
630
|
NA
|
|
|